EasyManua.ls Logo

Allen-Bradley Powermonitor 3000 - Page 196

Allen-Bradley Powermonitor 3000
356 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1404-UM001D-EN-E - October 2004
A-22 Powermonitor 3000 Data Tables
Table A.14 Metering Real and Apparent Energy Results
CSP File No. N20
Remote I/O BT 29
CIP Assy. Inst. 19 (Write), 20 (Read)
No. of Elements 23
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type All
Element
No.
Modbus
Address
Element Name Range Units Default
Value
Comment
0 40501 Password 0 to 9999 - 0 Required to clear or preset energy counters.
Returns -1.
1 40502 Parameter select 0 to 7
(bitfield)
- Refer to How to Clear or Preset Energy
Counters Using Communications on
page 4-52.
2 40503
KWh forward ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999 to 999 kWh
3 40504
4 40505
5 40506
6 40507
7 40508
KWh reverse ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999 to 999
8 40509
9 40510
10 40511
11 40512
12 40513
Kwh net ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999 to 999
13 40514
14 40515
15 40516
16 40517
17 40518
KVAh ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10-
3
-999 to 999 KVAh
18 40519
19 40520
20 40521
21 40522
22 40523 Metering iteration 0 to 32767 - Increments by 1 to 32767, rolls over to 0