Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-23
Table A.15 Metering Reactive Energy and Amp-Hour Results
CSP File No. N21
Remote I/O BT 30
CIP Assy. Inst. 21 (Write), 22 (Read)
No. of Elements 23
User Configurable No
Data Type Integer
Data Access Read/Write
PM3000 Type All
Element
No.
Modbus
Address
Element name Range Units Default
Value
Comment
0 40601 Password 0 to 9999 - 0 Required to clear or preset energy counters.
Returns -1.
1 40602 Parameter select 0 to 7 - Refer to How to Clear or Preset Energy
Counters Using Communications on
page 4-52.
2 40603
KVARh forward ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999 to 999 kVARh
3 40604
4 40605
5 40606
6 40607
7 40608
KVARh reverse ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999 to 999
8 40609
9 40610
10 40611
11 40612
12 40613
KVARh net ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999 to 999
13 40614
14 40615
15 40616
16 40617
17 40618
KAh ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999 to 999 kAh
18 40619
19 40620
20 40621
21 40622
22 40623 Metering iteration 0 to 32767 - Increments by 1 to 32767, rolls over to 0