Publication 1404-UM001D-EN-E - October 2004
A-42 Powermonitor 3000 Data Tables
14 31029-30 User selected parameter #15 - DeviceNet supports a maximum of 14 user-configured parameters.
15 31031-32 User selected parameter #16 -
16 31033-34 User selected parameter #17 -
17 31035-36 User selected parameter #18 -
18 31037-38 User selected parameter #19 -
19 31039-40 User selected parameter #20 -
20 31041-42 User selected parameter #21 -
21 31043-44 User selected parameter #22 -
22 31045-46 User selected parameter #23 -
Element
No.
Modbus
Address
Element name Range Comment
Table A.32 Write Error Status
CSP File No. N32
Remote I/O BT 4
CIP Assy. Inst. 38
No. of Elements 2
User Configurable No
Data Type Integer
Data Access Read only
PM3000 Type All
Element
No.
Modbus
Address
Element name Range Default
Value
Comment
0 31101 File, instance or BT
number
See Table A.1 -
-
Identifies data table written to last, value depends on comms
type. For Modbus, starting address of table written to last.
1 31102 Offending Element -1 = Last write was successful
0 to 26 = first unacceptable element of unsuccessful write
For Remote I/O Only:
0 = Last write was successful
1 t0 27 = First unacceptable word of unsuccessful write
For Modbus Only:
-1 = Last write was successful
40001 to 42001 - first unacceptable address of unsuccessful write.