Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-43
Table A.33 Harmonic Analysis Configuration/Read-Back Select
CSP File No. N33
Remote I/O BT 14
CIP Assy. Inst. 39 (Write), 40 (Read)
No. of Elements 9
User Configurable No
Data Type Integer
Data Access Read /Write
PM3000 Type See table
Applies to: Table A.34 (All models)
Table A.35,Table A.36, Table A.37, Table A.38 (M6 & M8)
Table A.48, Table A.49 (M8 only)
Element
No.
Modbus
Address
M4
M5
M
6
M
8
Element name Range Default
Value
Comment
0 41201 ••Password 0 to 9999 0 Required for configuration, -1 for readback
select, returns -1.
1 41202 ••Channel 1 to 9 1 Refer to Configuring Harmonic Analysis on
page 8-10
2 41203 ••Read-back mode 0 to 1 0
3 41204 Reserved 0 0
••Individual harmonic data type 0 to 1 0
4 41205 Reserved 0 0
••Enable/disable Harmonics 0 to 1 1
5 41206 Reserved 0 0
••IEEE-519 Max I
sc
Integer 0 to 9999 0
6 41207 Reserved 0 0
••IEEE-519 Max I
sc
Exponent -4 to 21 0
7 41208 Reserved 0 0
••IEEE 519 Max I
dmnd
Integer 0 to 9999 0
8 41209 Reserved 0 0
••IEEE 519 Max I
dmnd
Exponent -4 to 21 0