EasyManua.ls Logo

Allen-Bradley Powermonitor 3000 - Page 218

Allen-Bradley Powermonitor 3000
356 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1404-UM001D-EN-E - October 2004
A-44 Powermonitor 3000 Data Tables
Table A.34 Harmonic Results; THD, Crest Factor, and More
CSP File No. F34
Remote I/O BT 23
CIP Assy. Inst. 41
No. of Elements 9 (M4, M5); 10 (M6, M8)
User Configurable No
Data Type Floating Point
Data Access Read only
PM3000 Type See table
Element
No.
Modbus
Address
M4
M5
M
6
M
8
Element name Range Comment
0 31201-02 ••Channel number 1 to 9 Refer to Reading Harmonic Analysis Data on page 8-11
1 31203-04 ••% IEEE THD 0.0 to 1000.0
2 31205-06 ••% IEC thd (DIN) 0.0 to 1000.0
3 31207-08 ••Crest Factor 0.0 to 10.0
4 31209-10 ••THD & Crest iteration 0 to 32767
5 31211-12 Reserved 0
••TIF
0.0 to 999.9x10
22
6 31213-14 Reserved 0
••K-Factor
0.0 to 999.9x10
22
7 31215-16 Reserved 0
••IEEE-519 TDD
0.0 to 999.9x10
22
8 31217-18 Reserved 0
••IEEE-519 Pass/Fail -1 to 1
9 31219-20 Reserved 0
••FFT iteration 0 to 32767

Table of Contents