EMERGENCY SHUTDOWN
BATTERY
Breaker OFF
1
REMOVE
AC line
power cord
2
IMPORTANT
THE UPS CONTAINS MORE THAN ONE LIVE CIRCUIT.
DURING AN EMERGENCY, UTILITY POWER MAY BE
DISCONNECTED AT THE SERVICE ENTRANCE OR MAIN
ELECTRICAL PANEL TO PROTECT EMERGENCY
PERSONNEL; HOWEVER, POWER WILL STILL BE PRESENT
AT THE UPS OUTPUT.
TO PREVENT THE POSSIBILITY OF INJURY TO SERVICE OR
EMERGENCY PERSONNEL, ALWAYS SWITCH THE UPS
REAR PANEL BATTERY CIRCUIT BREAKER(S) OFF TO DE-
ENERGIZE THE CIRCUIT.
EMERGENCY SHUTDOWN PROCEDURE:
1. Switch the rear panel BATTERY circuit breaker OFF.
2. Unplug the AC power cord from the wall receptacle or the
back of the unit. If hardwired, switch the main panel AC
breaker to the UPS OFF.
On units equipped with an Emergency Power Off option:
Press the wall-mounted EPO switch (RED) to automatically
deactivate the CFR’s Battery Circuit.
EMERGENCY SHUTDOWN