34
8.26 CONDENSATE TRAP - Fig. 14
1. Gain access behind the front casing as described in Section 8.1.
2. Disconnect the top and drain connection of the condensate trap.
3. Place a container under the boiler and unscrew the bowl at the bottom of the trap, see Fig. 14. Some water will spill from
the trap.
4. Remove the screw securing the trap to the bottom of the boiler casing and lift out the trap.
5. Fit the new trap in reverse order.
Note: Fill the new trap with water once installed.
Alpha CD12S/20S/28S - Component Replacement