Heating on
This setting controls the temperature at which the heating is switched back on after the set
temperature is reached e.g. if the temperature is set to 20⁰C the heating will be held off until
the room temperature falls by the amount set . For example; a 0.5⁰C setting means that the
heating will switch on when the temperature falls to 19.5⁰C.
Turn the knob to H On 03, press the knob and the temperature will be displayed, turn the knob
to adjust the temperature and press the knob to store.
Room Temperature Sensor Calibration
Turn the knob to CALI 04, press the knob to enter menu and the temperature will appear. It is
now possible to turn the knob to adjust the calibration of the temperature sensor. Note; this
must be set using an accurate thermostat for comparison. When the temperature is set, press
the knob to store.
TECHNICAL SPECIFICATIONS
RECEIVER
Linked with transmitter via RF: frequency 868 MHz
Power rating: 230 VAC ± 10%, 50 Hz
Power consumption: 1.2 W
Relay switching capacity: Max 1A at 230 VAC
TRANSMITTER
Linked with receiver via RF: frequency 868 MHz
Power rating: 2 x 1.5AA - Alkaline batteries
Temperature setting: 3°C to 35°C in 0.2°C increments.
Display temperature: -9.9°C to 50°C in 0.2°C increments.
Approved for use: CE, LVD and EMC
EASY – STAT inst 1014 rev 01