P50 Agile P15D
7 Protection Parametre Settings
P15D/EN TM/B
7-13
Sr. No Parameter Default setting Setting Range
18. IN>1 TMS 0.1 0.025 to 1.2 step 0.005
This setting determines the new time multiplier setting to adjust the operating time of the IEC IDMT characteristic during the tclp time.
19. IN>2 Status Enabled Block / Enabled
The IN>2 status cells have two setting options, "Enable" and "Block". Selecting "Enable" for a particular stage means that the current
and time settings programmed in the following cells will be those that are adopted during the "tclp" time. Selecting of "Block" simply
blocks the relevant protection stage during the "tclp" time. It also removes the following current and time settings for that stage from the
menu.
20. IN>2 Current Set 0.2*In 0.20 to 4.00*In step 0.01*In
This setting determines the new pick-up setting for second stage earth fault element during the tclp time delay.
21. IN>2 Time Delay 0.01 000.00 to 200.00s step 0.01s
This setting determines the new operating time delay for the second stage definite time element during the tclp time.
22. IN>2 TMS 0.1 0.025 to 1.200 step 0.005
This setting determines the new time multiplier setting to adjust the operating time of the IEC IDMT characteristic during the tclp time.
23. IN>3 Status Enabled Block / Enabled
The IN>3 status cells have two setting options, "Enabled" and "Block". Selecting "Enable" for a particular stage means that the current
and time settings programmed in the following cells will be those that are adopted during the "tclp" time. Selecting "Block" simply blocks
the relevant protection stage during the "tclp" time. It also removes the following current and time settings for that stage from the menu.
24. IN>3 Current Set 0.2*In 0.20 to 4.00*In step 0.01*In
This setting determines the new pick-up setting for third stage earth fault element during the tclp time delay.
25. IN>3 Time Delay 0.01 000.00 to 200.00s step 0.01s
This setting determines the new operating time delay for the third stage definite time element during the tclp time.
26. IN>3 TMS 0.1 0.025 to 1.200 step 0.005
This setting determines the new time multiplier setting to adjust the operating time of the IEC IDMT characteristic during the tclp time.