P50 Agile P15D
8 Monitoring & Control
P15D/EN TM/B
8-7
will remain closed even if there is no power supplied to relay. The contact can be reset by pressing
RESET key after normalization of the relay power supply.
2.6 Remote trip
A dedicated binary input is provided marked as remote trip. After applying auxiliary voltage to this
terminal, the relay will provide an instant trip. This can be used for initiating trip from remote signal as
well for safety functions such transformer door monitoring.