12 SCADA Communications
P50 Agile P15D
12-6
P15D/EN TM/B
Sr.No. Function
Code
Register No. of
Regs
Format Reg.
Type
Address
Map
4
Status and
Logical Status
02
General Start 1 1 bit R 1x32769
Start R 1 1 bit R 1x32770
Start Y 1 1 bit R 1x32771
Start B 1 1 bit R 1x32772
Start I>1 1 1 bit R 1x32773
Start I>2 1 1 bit R 1x32774
Start I>3 1 1 bit R 1x32775
Start IN>1 1 1 bit R 1x32776
Start IN>2 1 1 bit R 1x32777
Start IN>3 1 1 bit R 1x32778
CLP in Progress 1 1 bit R 1x32779
Start I< 1 1 bit R 1x32780
TH Alarm 1 1 bit R 1x32781
General Trip 1 1 bit R 1x32782
Trip R 1 1 bit R 1x32783
Trip Y 1 1 bit R 1x32784
Trip B 1 1 bit R 1x32785
Trip I>1 1 1 bit R 1x32786
Trip I>2 1 1 bit R 1x32787
Trip I>3 1 1 bit R 1x32788