5 STANDARDS COMPLIANCE
Compliance with the European Commission Directive on EMC and LVD is demonstrated using a Technical
File.
5.1 EMC COMPLIANCE: 2004/108/EC
Compliance with EN60255-26:2009 was used to establish conformity.
5.2 PRODUCT SAFETY: 2006/95/EC
Compliance with EN60255-27:2005 was used to establish conformity.
Protective Class
IEC 60255-27: 2005 Class 1 (unless otherwise specified in equipment documentation). This equipment
requires a protective conductor (earth) to ensure user safety.
Installation category
IEC 60255-27: 2005 Overvoltage Category 3. Equipment in this category is qualification tested at 5kV peak,
1.2/50
m
S,
500 Ohms, 0.5 J, between all supply circuits and earth and also between independent circuits.
Environment
IEC 60255-27: 2005, IEC 60255-26:2009. The equipment is intended for indoor use only. If it is required for
use in an outdoor environment, it must be mounted in a specific cabinet or housing which will enable it to
meet the requirements of IEC 60529 with the classification of degree of protection IP54.
5.3 R&TTE COMPLIANCE
Radio and Telecommunications Terminal Equipment (R&TTE) directive 99/5/EC.
Conformity is demonstrated by compliance to both the EMC directive and the Low Voltage directive, to zero
volts.
5.4 UL/CUL COMPLIANCE
If marked with this logo, the product is compliant with the requirements of the Canadian and USA
Underwriters Laboratories.
The relevant UL file number and ID is shown on the equipment.
5.5 ATEX COMPLIANCE
If marked with the logo, the equipment is compliant with article 192 of European directive 94/9/EC. It is
approved for operation outside an ATEX hazardous area. It is however approved for connection to Increased
Safety, "Ex e", motors with rated ATEX protection, equipment category 2, to ensure their safe operation in
gas zones 1 and 2 hazardous areas.