P50 Agile P15D
5 Configuration
P15D/EN TM/B
5-7
2.1 Changing the settings
The general procedure for changing settings is explained with an example:
Example: Changing setting for Trip Test function
Step 1: Select CB CONTROL Menu
CB CONTROL
Step 2 : Press the Left arrow key (
). And password window will appear
Step 3: S
et the desired value
using the Plus / Up arrow key (+ /
) or the Minus / Right arrow key
(- /
)
Step 4 : After setting the desired password press the Edit Key, and the text or number
will
stop blinking
.
Step 5: Press the Left arrow key (
) and the Trip Test window will appear
Step 6: Press the Edit Key. The text will start blinking and the display will show the following:
Trip Test
Enabled
Step 7: The desired selection can be set using the Plus / Up arrow key (+ /
) or the Minus /
Right arrow key (- /
)
as shown in the display:
Trip Test
Enabled
Password
0001
Password
0000
Password
0000
Trip Test
Enabled
Trip Test
Disabled