Specification / Especificaciones:
Type
DIN 48*48
DIN 72*72 /48*96 /96*96
DIN 24*48
Model
NT-48RV-AF
NT-XX-RV-AF
NT-10-AF
Output method
Relay & SSR
Relay or SSR
Rated current
Relay 5A/250VACSSR30mA/12V
Operating voltage
90~265VAC 50/60Hz
Alarm output
Relay 5A/250VAC
Control method
PID + Fuzzy
Input method
PT / K / J / R / S / T/ B / E / N / L Selectable
Display range
-999 ~ 9999 -99.9 ~ 999.9 Selectable
Accuracy of display
± ( 0.1 % of F.S. + 1 DIGIT)
Setting range
-999 ~ 9999 -99.9 ~ 999.9 Selectable
Dielectric strength
Over 2.5KV
Isolation strength
Over 100MΩ / 500VDC
Operating temp
20 ~ 80℃;35 ~ 85RH
Housing material
Intensive PC+ABSUL-94V0
Mode of alarm / Modos de Alarma
ALt
Description / Descripción
Description / Descripción
ALt
Description / Descripción
0
AL1 ON
SV (SV+AL1)
AL2 ON
SV (SV+AL2)
AL1 ON
(SV - AL1) SV
AL2 ON
SV (SV+AL2)
2
AL1 ON
(SV - AL1) SV
AL2 ON
(SV AL2) SV
3
AL1 ON
(SV AL2) SV (SV+AL1)
AL2 ON
SV (SV+AL2)
AL1 ON
(SV AL1) SV (SV+AL1)
AL2 ON
SV SV+AL2
5
AL1 ON
(SV - AL1) SV (SV+AL1)
AL2 ON
SV (SV+AL2)
6
AL1 ON
AL1
AL2 ON
AL2
AL1 ON First cycle unable
AL1
AL2 ON
AL2
8
AL1 ON First cycle unable
(SV - AL1) SV
AL2 ON
SV (SV+AL2)
9
AL1 ON First cycle unable
(SV - AL1) SV (SV+AL1)
AL2 ON
SV (SV+AL2)
10
AL1 ON
SV (SV+AL1)
AL2 ON
SV tnr 99h59m
11
AL1 ON
AL1
AL2 ON
AL2
12
AL1 ON
AL1
AL2 ON
AL2
13
AL1 ON
SV (SV+AL1)
AL2 ON
(SV AL2) SV
14
AL1 ON
SV (SV+AL1)
AL2 ON
(SV AL2) SV
15
AL1 ON 1 Flicker
SV (SV+AL1)
AL2 ON
SV (SV+AL2)
16
AL1 ON
SV (SV+AL1)
AL2 ON
SV tnr 99h59m
17
AL1 ON
SV (SV+AL1)
AL2 ON
SV tnr 99m59s
18
AL1 ON
SV (SV+AL1)
AL2 ON
SV tnr 99m59s
19
Non-used
20
AL1 ON 1 Flicker
SV (SV+AL1)
AL2 ON
SV (SV+AL2)
21
AL1 ON 1 Flicker
SV (SV+AL1)
AL2 ON First cycle unable
(SV - AL1) SV (SV+AL2)
22
AL1 ON 1 Flicker
SV (SV+AL1)
AL2 ON
(SV - AL1) SV
23
AL1 ON 1 Flicker
SV (SV+AL1)
AL2 ON
(SV - AL1) SV
24
AL1 ON 1 Flicker
SV (SV+AL1)
AL2 ON
(SV - AL1) SV (SV+AL2)
25
AL1 ON 1 Flicker
SV (SV+AL1)
AL2 ON
(SV - AL1) SV (SV+AL2)
26
AL1 ON
AL1 SV
AL2 ON First cycle unable
(SV AL2) SV
1.ALt=15」: t = ON time of AL2 for cooling, OFF time is controlled by PID.
2.ALHHysteresis of alarm. Ex. PV(SV+AL1)→AL1 ON, PV(SV+AL1-ALH)→AL1 OFF
3.tnu= Process time of tnr, iftnutnrAL2 is turned ON or OFF
UL CE
RoHs
Instruction Manual / Manual de Uso
F - 71
NT-XX-RV-AF series All function temperature controller
Thank you very much for using FOTEK NT-XX-RV series All function Temperature controller
Please read this instruction manual before operating it to avoid from the malfunction.
FOTEK NT10-R-AF / NT-22-R-AF / NT-48RV / NT-72-RV / NT-20-RV / NT-21-RV / NT96-RV-AF
AlltronicsPerú
AUTOMATIZACIÓN INDUSTRIAL
https://www.fotek.com.tw
https://alltronicsperu.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Altronics FOTEK NT-RV Series and is the answer not in the manual?

Altronics FOTEK NT-RV Series Specifications

General IconGeneral
BrandAltronics
ModelFOTEK NT-RV Series
CategoryController
LanguageEnglish