- 4 - 02 ULADA Application Guide
5. Synchronizing NAC Power Extender Using Built-in Sync Protocol:
AL602/AL802/1002ULADA(J)/R1002ULADA have built-in protocols to support Amseco, Gentex
®
, System
Sensor
®
, Wheelock
®
two-wire synchronizable devices, therefore an external sync module is not required (Output
Programming Selection Table, pg. 5). In these modes Input 1 is always used to activate visual notification appli-
ances (strobes) and Input 2 is used to activate and silence audible notification appliances (strobes).
Note: Input 1 has to be activated in all the configurations.
SW1SW2
+ OUT1 --
IN1+
IN1--
IN2--
IN2+
C "DRY1" NC
RET1+
RET1--
RET2--
RET2+
C "DRY2" NC
+ OUT2 --
+ OUT3 --
+ OUT4 --
UPPER TERMINALS
LOWER TERMINALS
SW1SW2
+ OUT1 --
IN1+
IN1--
IN2--
IN2+
C "DRY1" NC
RET1+
RET1--
RET2--
RET2+
C "DRY2" NC
+ OUT2 --
+ OUT3 --
+ OUT4 --
UPPER TERMINALS
LOWER TERMINALS
2.2K
EOL
2.2K
EOL
2.2K
EOL
2.2K
EOL
2.2K
EOL
2.2K
EOL
To EOL or next
NAC Power Extender
Class B configuration only
NAC Power Extender:
DIP Switches set for desired Sync Protocol (ex. Gentex
®
,
System Sensor
®
, Amseco, CooperWheelock
®
).
NAC Power Extender:
DIP Switches set for Input to Output Follower Mode
Control Circuit
No Notification Appliances
Allowed
FACP
(Fire Alarm
Control Panel)
FACP EOL
For Class A
Configuration
return to FACP
FACP EOL
For Class A
Configuration
return to FACP
ON
1
ON
1
ON
1
ON
1
Fig. 5a
When connecting, keep wires on different sides of the screws in order to maintain loop integrity supervision.
DO NOT LOOP CONTINUOUS WIRE AROUND THE SCREW.
IN1+
IN1--
IN2--
IN2+
C "DRY1" NC
RET1+
RET1--
RET2--
RET2+
C "DRY2" NC
UPPER TERMINALS
LOWER TERMINALS
EOL or
Next Device
Control Circuit
NO Notification
Appliances allowed
FACP
For Class A configuration return to FACP
Fig. 6a
6. Using a Single FACP Output:
When only one FACP output is available, you may connect both Input 1 and Input 2 to it.
Wire [RET1 +] and [RET1 ] to [INP2 +] and [INP2 –].
Both visual and audible notification appliances will be activated simultaneously (Fig. 6a).

Other manuals for Altronix AL1002ULADAJ

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Altronix AL1002ULADAJ and is the answer not in the manual?

Altronix AL1002ULADAJ Specifications

General IconGeneral
BrandAltronix
ModelAL1002ULADAJ
CategoryExtender
LanguageEnglish

Related product manuals