RP/IS-A-4000SS/5000SS
4000SS
Installation, Maintenance, & Repair
Series 4000SS/5000SS
Reduced Pressure Zone Assemblies & Reduced Pressure Detector Assemblies
Sizes: 2
1
2" – 6" (65 – 150mm)**
NOTICE
For Australia and New Zealand, line strainers should be installed
between the upstream shutoff valve and the inlet of the backflow
preventer.
NOTICE
The flange gasket bolts for the gate valves should be
retightened during installation as the bolts may have loosened
due to storage and shipping.
Testing
For field testing procedure, refer to Ames installation sheets
IS-A-ATG-1 found on www.amesfirewater.com.
For other repair kits and service parts, refer to our Backflow
Prevention Products Repair Kits & Service Parts price list
PL-A-RP-BPD found on www.amesfirewater.com.
For technical assistance, contact your local Ames representative.
** Metric Dimensions are nominal pipe diameter. This product is produced with
ASME/ANSI flanged end connections.
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can
result in death, serious personal injury, property damage, or
damage to the equipment.
Keep this Manual for future reference.
You are required to consult the local building and plumbing
codes prior to installation. If the information in this manual
is not consistent with local building or plumbing codes,
the local codes should be followed. Inquire with governing
authorities for additional local requirements.
WARNING
!
Need for Periodic Inspection/Maintenance: This product must
be tested periodically in compliance with local codes, but at least
once per year or more as service conditions warrant. If installed on
a fire suppression system, all mechanical checks, such as alarms
and backflow preventers, should be flow tested and inspected in
accordance with NFPA 13 and/or NFPA 25. All products must be
retested once maintenance has been performed. Corrosive water
conditions, and/or unauthorized adjustments or repair could render
the product ineffective for the service intended. Regular checking
and cleaning of the product’s internal components helps assure
maximum life and proper product function.
WARNING
!
www.amesfirewater.com
A Watts Water Technologies Company
WARNING
!
The installation and maintenance of backflow assemblies
should be performed by a qualified, licensed technician.
Failure to do so may result in a malfunctioning assembly.

Questions and Answers

  • J
    Jacob MirandaJul 29, 2025
    What to do if the AMES Silver Bullet 4000SS Security Sensors pressure relief valve does not close?
    • K
      Kyle LewisJul 29, 2025
      If the pressure relief valve isn't closing, it could be due to several reasons: debris on the sealing surface, a plugged hydraulic hose, a damaged seat or rubber shut off disc, a ruptured diaphragm, or a wrinkled/improperly installed diaphragm. Try removing the relief valve and cleaning it. Also, disassemble and clean the hydraulic hose. If needed, replace the relief valve assembly or the diaphragm, ensuring proper positioning during reinstallation.
  • J
    Jennifer SandersAug 6, 2025
    Why is the AMES Silver Bullet 4000SS Security Sensors assembly discharging from the differential relief valve when there is no flow?
    • J
      Jeanne WilsonAug 6, 2025
      The assembly might discharge from the differential relief valve during no flow due to several reasons: a fouled first check, fluctuating inlet pressure, outlet pressure higher than inlet pressure and leak in No. 2 check valve, leak through the diaphragm or around flange bolt holes of relief valve, or the pressure relief valve not closing. You can try to disassemble and clean No. 1 check valve. Also, control the supply line water pressure. Disassemble, clean #2 check valve & identify cause of back pressure. For servicing the relief valve, refer to page 3.
  • P
    Phillip MurphyAug 13, 2025
    How to fix AMES Silver Bullet 4000SS Security Sensors assembly discharging from differential relief valve during flow?
    • M
      Marcus HarperAug 13, 2025
      If the assembly discharges from the differential relief valve during a flow condition, it could be because No. 1 check valve is wedged open, the O-ring is displaced from the groove in the 1st check, the pressure relief valve isn't closing, or there's fluctuating line pressure. Try disassembling and cleaning No. 1 check valve. If needed, disassemble and replace the O-ring.
  • B
    Brittany HawkinsAug 20, 2025
    What to do if AMES Silver Bullet 4000SS Security Sensors differential pressure relief valve doesn't open during test?
    • S
      Sean TaylorAug 20, 2025
      If the differential pressure relief valve doesn't open during the test, it might be due to differential pressure across No. 1 check valve staying above 2psi because of a leaking outlet gate valve, a weak or broken relief valve spring, a shut off seat tube bound in the body, or a plugged hydraulic hose. You can try to repair the shut-off valves. Also, disassemble and replace the relief valve spring. Disassemble and repair the shut off seat tube and the hydraulic hose.

Summary

Product Overview and Safety

General Safety and Compliance

Key safety instructions, warnings, and compliance with local building and plumbing codes.

Installation and Service Recommendations

Notices on flange bolt retightening, line strainer placement, and references for testing and repair.

Installation Guidelines

Pre-Installation Procedures

Steps before installation: line flushing, clearance requirements, and system purging for fire protection.

Installation Configurations

Guidelines on approved horizontal installation, clearance, and considerations for pit installations.

Maintenance Instructions

Depressurize Valve Before Servicing

Critical safety procedure to depressurize the valve before commencing any maintenance or repair.

Cam-Check Component Service

Detailed instructions for removing, cleaning, and reassembling the internal Cam-Check components.

Relief Valve Service

Relief Valve Disassembly

Step-by-step guide for safely disassembling the relief valve assembly for inspection or repair.

Relief Valve Reassembly

Instructions for cleaning, inspecting, and correctly reassembling the relief valve components.

Testing Procedures

Differential Pressure Testing

Procedures for testing check valve tightness, backflow prevention, and relief valve operation.

Troubleshooting

Problem Identification and Solutions

Identifies common assembly problems, their causes, and recommended solutions.

Differential Pressure Gauge Readings

Interpreting differential pressure gauge readings and their implications for valve function.

Additional Information and Warranty

Website and Contact Information

Provides website for additional details and contact information for technical assistance.

Limited Warranty Terms

Outlines the product's limited warranty period, coverage, and exclusions.

AMES Silver Bullet 4000SS Series Specifications

General IconGeneral
ModelSilver Bullet 4000SS Series
TypeMicrowave motion sensor
Frequency10.525 GHz
Power Source12-24 VDC
CategorySecurity
Operating Temperature-40°F to 140°F (-40°C to 60°C)
OutputRelay
MountingSurface mount