Do you have a question about the Ampac EV3000 154-0258 and is the answer not in the manual?
Wire the Common (TB1/2) of the EV3000 Battery Detector to the Battery Isolator / Trip Switch Input.
Wire the N/O (TB1/3) to the 6 Amp Power Supply Circuit Breaker terminal (CB TB2/8).
Wire the N/C (TB1/4) to the Battery Monitoring Fuse (250mA).
Connect hookup wire from Battery Monitoring Fuse (250mA) to the common (TB1/2).
Power up FACP, connect batteries, then test by disconnecting battery to ensure fault.
Wire the Common (TB1/2) of the EV3000 Battery Detector to the Battery Isolator / Trip Switch Input.
Wire the N/O (TB1/3) to the 6 Amp Power Supply Circuit Breaker terminal (CB TB2/8).
Wire the N/C (TB1/4) to the Battery Monitoring Fuse (250mA).
Connect hookup wire from Battery Monitoring Fuse (250mA) to the common (TB1/2).
Power up FACP, connect batteries, then test by disconnecting battery to ensure fault.