EasyManua.ls Logo

Ampcontrol Gasguard 2 - Page 19

Ampcontrol Gasguard 2
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ampcontrol Pty Ltd ABN 28 000 915 542
GG2 COMMUNICATIONS USER MANUAL
GG2B032
Version 1 JULY/2020
Uncontrolled Copy - Refer to Ampcontrol Website for Latest Version
APPROVED FOR EXTERNAL DISTRIBUTION
PROPERTY OF AMPCONTROL PTY LTD
NOT TO
BE REPRODUCED IN PART
Register
Description
R/W
Detail
Format
SCADA*
6 bit 8
4-20mA loop fault
R
1 = 4-20mA loop fault
bit
i6 bit 9
Latched catalytic detector
R
1 = detector latched
bit
6 bit 10
Hardware fault
R
1 = fault
bit
6 bit 11
Detector warmup
R
1 = in warmup
bit
6 bit 12
Data valid
R
1 = data valid
bit
6 bit 13
Sensor aged. Sensor
performance has
deteriorated due to age.
R
1 = sensor aged
bit
6 bit 14
Out of operational temp
range.
R
1 = temp out of range
bit
6 bit 15
Telemetry test active
R
1 = telemetry test in
progress
bit
7
RESERVED
8 bit 0
System bypass
R/W
Write 1 to put device into
bypass. Write 0 to leave
bypass.
bit
8 bit 1
Reset latched catalytic
R/W
Write 1 to activate the
reset, the value should
clear to 0.
bit
9 bits 0-
7
FACTORY USE ONLY
9 bit 8
Atmospheric pressure
fluctuation too great to
obtain stable reading
R
1 = true
bit
9 bit 9
Sensor reading has gone
above 100%
R
1 = above range
bit
9 bit 10
Sensor reading has gone
below -10%. Auto clears
when reading goes above
0%
R
1 = under range
bit
9 bit 11
FACTORY USE ONLY
9 bit 12
Unexpected calibration
values
R
1 = calibration values
are not correct
bit
9 bits
13-15
RESERVED
10 bits
0-11
FACTORY USE ONLY
10 bit 12
Detector warming up
1 = in warmup
bit
10 bit 13
Catalytic latch
1 = detector latched
bit
10 bit 14
Incomplete adjustment
(NDIR)
1 = adjustment
incomplete
bit
10 bit 15
FACTORY USE ONLY
11
Detector pressure
Hectopascals (hPa)
Signed Int
12
Detector temperature
Degrees Celsius(°C) *
100
Signed Int
13
Detector humidity
Permyriad
Signed Int
14
Detector bus voltage
Millivolts
Signed Int