AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96 13
Programming a Point, continued
Programming Control modules is similar to Monitor modules except the
default zone is always set to Zone 00 (General Alarm). The following is a
Programming Output Circuits (four NACs or Panel Output Circuits con-
nected through one of the panel NAC circuits) is like programming Control
Modulesexcept for the Type Code and device address.
Programming NAC/Panel
Output Circuits
The following table contains Control Module Type Codes:
A Release Ckt is always non-
silenceable.
edoCepyTnoitcnuFlaicepS
lortnoCCANdesivrepuS
yaleRtuptuoyaleR
tiucriClleBCANdesivrepuS
tkCebortSCANdesivrepuS
tiucriCnroHCANdesivrepuS
tkCelbiduACANdesivrepuS
rekaepSCANdesivrepuS
lleBdnEleRCANdesivrepuS
lebalknalbedoCepyTrehtoonnehwesu(CANdesivrepuS
)seilppa
tkCesaeleRrofdesivrepus,detimilrewopnon,tiucriCgnisaeleR
stluafdnuorgdna,strohs,snepo
CLUtkCleR,sneporofdesivrepus,detimilrewop,tiucriCgnisaeleR
stluafdnuorgdna,strohs
CmroF.aeleResaelernopuetarepostcatnoc,tuptuoyaleR
elbiduAleResaelernopudetavitca,CAN
ltCteseRnoNdnammocteseRmetsySybdetceffanu,tuptuoyaleR
enohpeleTtiucricenohpeletdradnatS
The table of Type Codes
contains a comprehensive
list of Type Codes. The
Type Codes that display,
however, depend on the
configuration.
Default parameters for the
Control Module Programming
screen follow:
Switch Inhibit (I) annuncia-
tors in the modules range
cannot activate;
Silenceable (S); and
Walk Test (*) not selected.
The Type Code selection blinks, meaning you can press the Next or Previous
keys to scroll through the Type Code selections. Refer to the table, Control
Module Type Codes. You can also do the following:
1) Use the arrow and alphanumeric keys to modify point information, such
as the CBE equation.
2) When finished modifying a point, press <Enter>; then use the Next and
Previous keys to select another point.
Silenceable (S=selected; *=off)
PROGRM CONTROL MODULE ADDRESS 108
Z00 Z Z Z Z IS * M108
Blinking Type Code Selection
Walk Test Selection (*=off;
W=Walk Test Selected)
Switch Inhibit (I=selected; *=off)
Defaults for the NAC/Panel
Output Circuits Screen include the
following:
Default zone selection is Z00
(general alarm); and
Walk Test (W) is selected.
PROGRM BELL CIRCUIT PANEL CIRCUIT NO. 3
Z00 Z Z Z Z IS W B03
Address of a NAC/Panel Output
Circuit connected through NAC1
(B01), NAC2 (B02), NAC3 (B03),
or NAC4 (B04)
Blinking Type Code Selection
Switch Inhibit (I=selected; *=off)
Silenceable (S=selected; *=off)
Walk Test Selection (*=off;
W=Walk Test Selected)
The Type Code selection blinks, meaning you can press the Next or Previous
keys to scroll through the Type Code selections. Refer to the table, NAC/
Output Circuit Type Codes.
Programming a Control
Module
Control Module Programming Screen
Control Module Type
Codes
Control Module Type Codes