AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96 13
Programming a Point, continued
Programming Control modules is similar to Monitor modules except the
default zone is always set to Zone 00 (General Alarm). The following is a
Programming Output Circuits (four NACs or Panel Output Circuits con-
nected through one of the panel NAC circuits) is like programming Control
Modulesexcept for the Type Code and device address.
Programming NAC/Panel
Output Circuits
The following table contains Control Module Type Codes:
A Release Ckt is always non-
silenceable.
edoCepyTnoitcnuFlaicepS
lortnoCCANdesivrepuS
yaleRtuptuoyaleR
tiucriClleBCANdesivrepuS
tkCebortSCANdesivrepuS
tiucriCnroHCANdesivrepuS
tkCelbiduACANdesivrepuS
rekaepSCANdesivrepuS
lleBdnEleRCANdesivrepuS
lebalknalbedoCepyTrehtoonnehwesu(CANdesivrepuS
)seilppa
tkCesaeleRrofdesivrepus,detimilrewopnon,tiucriCgnisaeleR
stluafdnuorgdna,strohs,snepo
CLUtkCleR,sneporofdesivrepus,detimilrewop,tiucriCgnisaeleR
stluafdnuorgdna,strohs
CmroF.aeleResaelernopuetarepostcatnoc,tuptuoyaleR
elbiduAleResaelernopudetavitca,CAN
ltCteseRnoNdnammocteseRmetsySybdetceffanu,tuptuoyaleR
enohpeleTtiucricenohpeletdradnatS
The table of Type Codes
contains a comprehensive
list of Type Codes. The
Type Codes that display,
however, depend on the
configuration.
Default parameters for the
Control Module Programming
screen follow:
Switch Inhibit (I) annuncia-
tors in the modules range
cannot activate;
Silenceable (S); and
Walk Test (*) not selected.
The Type Code selection blinks, meaning you can press the Next or Previous
keys to scroll through the Type Code selections. Refer to the table, Control
Module Type Codes. You can also do the following:
1) Use the arrow and alphanumeric keys to modify point information, such
as the CBE equation.
2) When finished modifying a point, press <Enter>; then use the Next and
Previous keys to select another point.
Silenceable (S=selected; *=off)
PROGRM CONTROL MODULE ADDRESS 108
Z00 Z Z Z Z IS * M108
Blinking Type Code Selection
Walk Test Selection (*=off;
W=Walk Test Selected)
Switch Inhibit (I=selected; *=off)
Defaults for the NAC/Panel
Output Circuits Screen include the
following:
Default zone selection is Z00
(general alarm); and
Walk Test (W) is selected.
PROGRM BELL CIRCUIT PANEL CIRCUIT NO. 3
Z00 Z Z Z Z IS W B03
Address of a NAC/Panel Output
Circuit connected through NAC1
(B01), NAC2 (B02), NAC3 (B03),
or NAC4 (B04)
Blinking Type Code Selection
Switch Inhibit (I=selected; *=off)
Silenceable (S=selected; *=off)
Walk Test Selection (*=off;
W=Walk Test Selected)
The Type Code selection blinks, meaning you can press the Next or Previous
keys to scroll through the Type Code selections. Refer to the table, NAC/
Output Circuit Type Codes.
Programming a Control
Module
Control Module Programming Screen
Control Module Type
Codes
Control Module Type Codes