AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96 21
The Disable/Enable option lets you disable or enable programmed
points for detectors, modules, and NAC/Panel Output Circuit mod-
ules.
1) Select <1> from the Status Change screen to display the Disable/
Enable screen:
2) Select the point type:
H for detectors
I for modules
J for output circuits
z for zones
The cursor will blink the first SLC address digit in the detector,
zone, module, or output circuit field.
3) Enter the address of the point, then press Enter. A sample display
follows:
You can disable or enable a point by changing the status banner as
follows:
Disable/Enable
The control panel leaves
Programming Mode and
returns to standard mode if
the keypad is not used for
more than 2 minutes.
3. Status Change
The program does not allow
changes to 1) initiating devices
in alarm; or 2) control points
that are on.
Continued on the next page...
1
STATUS CHANGE PRESS:1=DISABL 2=SENSITIV
3=CLR VER 4=CLR HIST 5=TIME 6=WALK TEST
Status Change provides a second programming levelaccessed by an
assigned passwordfor changing operating parameters. These
operating parameters do not affect control program settings.
Assign the Status Change password to persons who do not need to
do application programming or autoprogramming. For example, the
Status Change password lets someone change settings such as
detector sensitivity, system time and date, and so on.
From the Password Enter screen, enter the Status Change password
to display the Status Change screen:
STATUS CHANGE PRESS:1=DISABL 2=SENSITIV
3=CLR VER 4=CLR HIST 5=TIME 6=WALK TEST
Status Change Screen
Disable/Enable Screen
ENABLE MONITOR MODULE ADDRESS 101
ZO4 Z Z Z Z M101
Blinking Status Banner
...oT...sserP
sutatsehtegnahc
L
ro
M
sutatsehtevas
C
sserddatniopsuoiverprotxenehtotog
L
ro
M
How to disable or enable a point
Overview
ZONE=Z,AA,E DETECTOR=*,AAA,E
MODULE=#,AAA,E OUTPUT CKT=&,A-A,E
First address digit (typical)