8 AUTOPULSE IQ-396X Programming Doc. 50402:B 07/22/96
2. Program Change
Press <1>. The control panel displays the Enter Password screen.
Changing a Password
Enter Program Mode by pressing <Enter>. The control panel
displays the Program Entry screen:
Enter a password to enter Program Change or Status Change. In
Program Change or Status Change, the control panel does the
following:
activates the trouble relay (TB5 on the MPS-400);
shuts off the panel sounder; and
flashes the System Trouble LED (and cannot be made steady).
For example, if you enter a Program Change password, the control
panel displays the Program Change screen:
The IQ-396X provides two types of selectable passwords: Program
Change and Status Change. Refer to the following table for uses and
the factory-set password for each:
drowssaP
epyt
otdesuyrotcaf
gnittes
margorP
egnahC
)levelhgih(
otedomegnahCmargorPretnE
snoitcnuflenaplortnocmargorp
.sretemarapmetsystesdna
00000
egnahCsutatS
)levelwol(
tesotedomegnahCsutatSretnE
wolekamro,tsetklawretne,emit
.segnahcsutatslevel
11111
Entering a Password
Types of Passwords
For security purposes, you can change your passwords. Do so by
following the instructions in Password Change in the Program
Change section.
Program Entry Screen
1=PROGRAMMING 2=READ STATUS ENTRY
(ESCAPE TO ABORT)
ENTER PROG OR STAT PASSWORD, THEN ENTER.
(ESCAPE TO ABORT)
Enter Password Screen
How to Enter Program
Change
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE
5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG
If the Password does not work
The control panel displays: Incorrect
Password and a hexadecimal error
code number. Contact the manufac-
turer for assistance.
Program Change Screen