AUTOPULSE IQ-396X Operations Doc. 50403:B 07/22/96 9
If an SDX or CPX detector exceeds the programmed Pre-Alarm level, a
Pre-Alarm condition occurs: the panel sounder and zone F9 activate;
and the Pre-Alarm LED lights. Figure 12 shows a sample Pre-Alarm
messagesent to the LCD display, optional LCD-80, optional printer,
and history filefor a control panel programmed for an Alert Pre-Alarm.
Pre-Alarm Operation (AWACS)
Intelligent Detector Functions
Figure 12 shows a detectorprogrammed for a Pre-Alarm level of 5
that reaches 105% of the programmed Pre-Alarm level. The 105% is a
real-time display and tracks smoke levels.
If programming a control panel for an Action Pre-Alarm, the display
remains the same, but the word Action replaces Alert. The control
panel latches for Action Pre-Alarms and applies the programmed
control functions.
Figure 12: Alert Pre-Alarm message
PREALARM SMOKE (PHOTO) I.C.U WEST WING
ALERT 105%/5 12:01A 11/01/95 D101
ALERT Pre-Alarms automatically
restore.