12 AUTOPULSE IQ-396X Operations Doc. 50403:B 07/22/96
Read Status
Press <Enter>. The control panel displays the following screen:
Read Status functions do not require a password. The control panel will con-
tinue to provide fire protection while in Read Status. You can enter Read Status
while in Fire Alarm or Trouble mode. If a new alarm or trouble occurs during
these functions, the control panel automatically exits Read Status.
Overview
How to enter Read
Status
READ POINT=0 HIST=2 ALARM HIST=4 <ENTER>
PRNT POINT=1 HIST=3 ALARM HIST=5 <ENTER>
During all Read Status operations (except print operations) the control panel
starts a 2-minute timer each time you press a key. If the control panel does not
detect a key press for 2 minutes, the control panel leaves the current operation
and returns to the previous display.
Press <Esc> to delete the previous entry.
Press <System Reset> to abort Read Status.
Read Point options let you display point and zone status on the display, but the
information is not sent to the serial ports or the history file. To read the status
of points and zones, press <0> then <Enter> from the Read Status screen. The
control panel displays the Read Point screen (Figure 20):
Figure 20: Read Point Screen
...oT...sihtoD
tnioPdaeR
sserP.1
C0
sserP.2
IJHz
.sserddaenozroecivedehtretnE.3
stnioPtnirP
sserP
C1
yrotsiHdaeR
sserP
C2
yrotsiHtnirP
sserP
C3
yrotsiHmralAdaeR
sserP
C4
yrotsiHmralAtnirP
sserP
C5
Figure 19: Read Status Options
If attempting to read a
point that is not
installed, the control
panel displays NOT
INSTALLED.
ZONE=Z,AA,E DETECTOR=*,AAA,E
MODULE=#,AAA,E OUTPUT CKT=&,A-A,E
To read a detector, press H then enter the detector address.
To read a module, press I then enter the module address.
To read an output circuit, press J then enter the output circuit address.
1=PROGRAMMING 2=READ STATUS ENTRY
(ESCAPE TO ABORT)
Figure 17: Read Status Entry Screen
Press <2> and the control panel displays the following screen:
Figure 18: Read Status Screen
To do a Read Status, follow the instructions in Figure 19.
Read Status for Points
and Zones
Read Status
Options