16 AUTOPULSE IQ-396X Operations Doc. 50403:B 07/22/96
Read Status
Figure 30 shows the typical format for displaying software zone F7 (Holiday
zone):
Figure 30: Holiday Zone Screen
Figure 31 shows the typical format for displaying software zone F8 for NAC
coding:
Pre-Alarm Zone
OFF HOLIDAY FUNCT 01/01 04/14 05/29
06/03 07/04 09/04 11/23 11/24 12/25
A Day/month program selection for
holiday days of the year
OFF CODING FUNCTION CODE TYPE
MARCH TIME F08
The NAC coding selection indicates the type of coding applied to each of the
four panel NACs that list zone F8 in their CBE. Zone F8 does not affect
addressable control modules. NAC coding selections include the following:
March Time (default)  120 PPM (Pulses Per Minute)
Two-Stage  Alert signal (20 PPM); General Alarm signal (Steady on)
California  10 sec. on, 5 sec. off, repeats
Temporal  0.5 on, 0.5 off, 0.5 on, 0.5 off, 0.5 on, 1.5 off, repeats
Figure 32 shows the typical format for displaying software zone F9 (Pre-
Alarm):
You can list zone F9 in the CBE of any control point. The Pre-Alarm zone
turns on if any detector reaches a Pre-Alarm threshold. Zone F9 indicates
the beginning of an alarm, or when the detector needs maintenance.
OFF PRE-ALARM FUNCT ALERT
F09
NAC Coding Zone
Refer to the IQ-396X
Programming Manual for
information on Pre-Alarm
settings.
Indicates NAC
coding zone F8
Indicates the NAC
coding selection
Holiday Zones
Figure 32: Pre-Alarm Zone Screen
Figure 31: NAC Coding Zone Screen
Continued on the next page...