AUTOPULSE IQ-396X Operations Doc. 50403:B 07/22/96 15
Read Status
Figure 27 shows a typical format for displaying software zone F0 (Presig-
nal Delay):
Figure 27: Presignal Delay Screen
DELAY=180 shows the programmed Presignal delay of 180 seconds.
PAS=YES shows that Positive Alarm Sequence operation is selected in
the program; PAS=NO Positive Alarm Sequence operation not selected.
Releasing Zones
Presignal Delay
Time Control Zones
Figure 29 shows the typical format for displaying time control zones F5
and F6:
Figure 29: Time Control Screen
The Time Control screen provides the following information:
ON=7:00 OFF=18:00 shows the programmed timesin 24-hour
(military) formatwhen zone F5 automatically turns on and off each
day.
DAYS= MTWTF H shows the programmed days-of-week when the On/
Off times are effective. H is a holiday schedule defined by the pro-
gram for zone F7.
You can also select zone F5 or F6 for detector day/night sensitivity. For
example, you can do the following:
1) List zone F5 in the CBE of an initiating device, such as a smoke
detector.
2) Set the On time for F5 to 07:00 and the Off time for F5 to 19:00.
3) When zone F5 is active at 07:00, the control panel forces the detector
sensitivity of any initiating device listed for zone F5 to the least sensi-
tive setting. When zone F5 goes off at 19:00, the detector sensitivity
returns to its original setting.
OFF PRESIGNAL FUNCT PRESIGNAL DELAY
DELAY=180 PAS=NO F00
Figure 28 shows the typical format for displaying Releasing Zones R0-R9:
Figure 28: Releasing Zone Screen
DELAY=30 shows the programmed delay time, in seconds.
ABORT=ULI shows the abort function (ULI, IRI, NYC, or AHJ), if an
abort switch is mapped to this zone.
CROSS=Y indicates that cross zoning is used (requires two or more
detectors programmed to this zone in alarm to activate the zone).
SOAK specifies the Soak Timer (automatic shut off of device) value
(0000-9999seconds; 0000 = no Soak Timer).
Refer to the IQ-396X Program-
ming Manual for information
and instructions on Releasing
Zones and the Soak Timer.
OFF TIME FUNCTION TIME CONTROL
ON=07:00 OFF=18:00 DAYS= MTWTF H F05
The On time for devices
programmed for zone F5
The Off time for devices
programmed for zone F5
Refer to the IQ-396X Program-
ming Manual for information on
detector sensitivity settings.
Indicates zone F5
Holiday Schedule
defined by zone F7
OFF SOFTWARE ZONE RELEASE CONTROL
DELAY=30 ABORT=ULI CROSS=Y SOAK=0000 R0