EasyManua.ls Logo

Ansul AUTOPULSE IQ-396X - Read History Functions; History File Overview and Access Methods

Ansul AUTOPULSE IQ-396X
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14 AUTOPULSE IQ-396X Operations Doc. 50403:B 07/22/96
Read Status
The control panel maintains a history file of the last 800 events, each with a
time and date stamp. History events include the following:
All alarms, troubles and operator actions, such as: Acknowledge, System
Reset, Alarm Silence, Alarm Activate, and Walk Test.
Programming entries, along with a number (0-9) indicating the program-
ming submenu (for example, 0=Clear).
The control panel contains two event buffers: a History buffer that can store
up to 800 events (all types); and an Alarm buffer that can store up to 200
alarm events.
View Event History
From the Read Status screen, press <2>; then, press <Enter>. The control
panel displays the Event History screen (Figure 24):
Viewing and printing Hidden History is similar to Read Point. Once you
read a Hidden History, you can do the following:
Press L to view the next event in sequence; or
Press M to view the previous event in sequence.
EVENT HISTORY START
EVENTS IN HIST : 800
ALARM HISTORY START (ESCAPE TO ABORT)
ALARMS IN HIST : 200
...oT...sserP
yrotsihmralAneddiHdaeR
C6
yrotsihmralAneddiHtnirP
C7
lamroNneddiHdaeR
yrotsih
C8
lamroNneddiHtnirP
y
rotsih
C9
View or Print Hidden History
If you clear History, events remain in a shadow fileknown as a hidden
history file. To display or print a hidden history file, follow the instructions
in Figure 26. To clear the history file, refer to the instructions in the
IQ-396X Programming Manual.
Figure 24: Event History Screen
Figure 25: Alarm History Screen
Figure 26: Hidden History Selections
View Alarm History
From the Read Status screen, press <2>; then, press <Enter>. The control
panel displays the Event History screen (Figure 25):
The number of events in the
History buffer
The number of events in the
Alarm buffer
Read History