22 AUTOPULSE IQ-396X Operations Doc. 50403:B 07/22/96
Selecting AMG Group Functions
If a digitally-stored voice message
fails, the AMG-1 automatically
switches to the primary evacua-
tion tone, and generates a
trouble signal.
You can record custom messages through the AMG microphone or load a
message recorded on a standard audio cassette recorder. (To do so,
connect the cassette recorder to the AMG low-level input connector.)
1) Set the Voice RAM Enable switch to the ON position.
2) Record or download a message (up to 24 seconds long).
3) Set the Voice RAM Enable switch to the OFF position.
AMG-1 Board Components
Recording Custom Messages
(VRAM option)
AMG DIP Switch for loading
Custom messages
Voice Message #4 (VRAM-B)
Field-Programmable Message
(optional)
Voice Message #3 (VRAM-A)
Field-Programmable
Message (optional)
Microphone
Connector
VRAM Enable A
VRAM Enable B
Voice Message #1
Factory Programmed
EPROM
Not Used