PAGE 4
FRONT PANEL INDICATORS
009180
POWER LED:
GREEN, AMBER OR OFF
RELEASE FAULT LED:
OFF OR AMBER
DETECTION FAULT LED:
OFF OR AMBER
1) Power LED
a. Green steady-on indicates normal external power.
b. Amber pulsing 1 x 30 sec. indicates external power fault;
Sounder auto-silences after 10 min. to conserve power.
Amber pulsing 1 x 10 sec. indicates internal power fault;
sounder auto-silences after 10 min. to conserve power.
Power fault will continue for up to 72 hours as long as
fault exists or until unit powers down.
Contact Authorized ANSUL Distributor for service.
c. Off indicates no system power.
2) Release
!
and Detection Fault LEDs
a. Off indicates normal status.
b. Amber pulsing with sounder indicates a fault condition.
CAUTION
Any fault indication may cause the fire detection
and actuation system to not function properly;
immediately contact an Authorized ANSUL
Distributor for service.