USER’S GUIDE
network management card
62
Relays: Output Relays and Input Relays
From Device Manager, type 1 to select DC Power Plant. Then type 5 to
select Relays. The following options are displayed.
1- Input Relays
2- Output Relays
Type 1 for a menu of Input Relays, or type 2 for a menu of Output Relays,
including the Minor and Major Relay.
From either menu, to display the status (On or Off) and the following
configurable options of a relay, type the menu option number for that relay.
Menu Item Description
1- Name The name of the relay.
Maximum: 16 characters
2- Alarm Delay
(sec)
If the condition causing the alarm clears before this delay expires,
the Management Card does not initiate the action associated with
the alarm.
Minimum: 0 seconds
Maximum: 60.00 seconds
Note: If menu item 3- Alarm is set to M
AJOR or Minor, you cannot
configure an alarm delay
3- Alarm Allowed values: any standard alarm selection:
Major activates the major relay.
Minor activates the minor relay.
Relay 1 through Relay 6 activates the relay specified.
Ignore ignores the alarm.
Note: You cannot change this value for the Major or Minor Relay.
4- Accept
Changes
Use this option to save your changes.