EasyManuals Logo

APC AP9617 User Manual

APC AP9617
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
®
USER’S GUIDE
network management card
7
Watchdog Features
Overview
To detect internal problems and recover from unanticipated inputs, the
Management Card uses internal, system-wide watchdog mechanisms.
When it reboots itself to recover from an internal problem, a System:
Warmstart event is recorded in the Event Log.
Network interface watchdog mechanism
The Management Card implements internal watchdog mechanisms to
protect itself from becoming inaccessible over the network. For example, if
the Management Card does not receive any network traffic for 9.5 minutes
(either direct traffic, such as SNMP, or broadcast traffic, such as an Address
Resolution Protocol [ARP] request), it assumes that there is a problem with
its network interface and reboots itself.
Resetting the network timer
To ensure that the Management Card does not reboot if the network is quiet
for 9.5 minutes, the Management Card attempts to contact the Default
Gateway every 4.5 minutes. If the gateway is present, it responds to the
Management Card, and that response restarts the 9.5-minute timer. If your
application does not require or have a gateway, specify the IP address of a
computer that is running on the network most of the time and is on the same
subnet. The network traffic of that computer will restart the 9.5-minute timer
frequently enough to prevent the Management Card from rebooting.

Other manuals for APC AP9617

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC AP9617 and is the answer not in the manual?

APC AP9617 Specifications

General IconGeneral
TypeNetwork Management Card
ModelAP9617
Data Link ProtocolEthernet, Fast Ethernet
Network Ports Qty1
Network ProtocolsTCP/IP, HTTP, HTTPS, SNMP, Telnet, SSH
ManagementSNMP
CompatibilitySmart-UPS
Remote Management ProtocolSNMP, HTTP, HTTPS, Telnet, SSH
SecuritySSL, SSH
Operating Temperature0 to 45 °C
Storage Temperature-15 to 65 °C
Humidity0 to 95% non-condensing
PortsRJ-45 Ethernet