22 InRow™ Chilled Water Air Conditioners Technical Specifications 990-4618A-001
Recommended Capacity Limitations
ACRC100 series
ACRC500/ACRP500 series
IT Equipment IT Equipment Air Flow Recommended Capacity Limit
°C (°F) l/s per kW (CFM/kW) kW
11.0 (19.8) 75.5 (160) 18
11.3 (20.4) 73.2 (155) 19
11.7 (21.1) 70.8 (150) 19
12.1 (21.8) 68.4 (145) 20
12.5 (22.6) 66.1 (140) 21
13.0 (23.4) 63.7 (135) 21
13.5 (24.3) 61.4 (130) 22
14.1 (25.3) 59.0 (125) 23
14.6 (26.4) 56.6 (120) 24
15.3 (27.5) 54.3 (115) 25
15.9 (28.7) 51.9 (110) 26
16.7 (30.1) 49.6 (105) 28
17.5 (31.6) 47.2 (100) 29
IT Equipment IT Equipment Air Flow Recommended Capacity Limit
°C (°F) l/s per kW (CFM/kW) kW
11.0 (19.8) 75.5 (160) 43
11.3 (20.4) 73.2 (155) 45
11.7 (21.1) 70.8 (150) 46
12.1 (21.8) 68.4 (145) 48
12.5 (22.6) 66.1 (140) 49
13.0 (23.4) 63.7 (135) 51
13.5 (24.3) 61.4 (130) 53
14.1 (25.3) 59.0 (125) 55
14.6 (26.4) 56.6 (120) 58
15.3 (27.5) 54.3 (115) 60
15.9 (28.7) 51.9 (110) 63
16.7 (30.1) 49.6 (105) 66
17.5 (31.6) 47.2 (100) 69

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC InRow and is the answer not in the manual?

APC InRow Specifications

General IconGeneral
RefrigerantR410A
MountingIn-row
Humidity Range20% to 80% RH
AirflowVaries by model (e.g., 1, 500 to 6, 000 CFM)
Power Supply208/230V or 400/480V, 3-phase
Operating Temperature Range65°F to 95°F (18°C to 35°C)