990-4618A-001 InRow™ Chilled Water Air Conditioners Technical Specifications 23
Performance Specifications 5.6°C (42°F) EWT
Temperature DB,
WB
°C (°F)
CW
Delta T
°C (°F)
Model Series
Total Net Capacity
Sensible Net
Capacity
Sensible
Heat Ratio
CW
Flow Rate
Total CW
Pressure Drop
kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O)
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
5.5°C (10°F) ACRC100 17.0 (58000) 16.7 (57000) 0.98 0.78 (12.3) 44.79 (15.02)
6.6°C (12°F)
ACRC100 16.1 (55000) 16.1 (55000) 1.00 0.62 (9.7) 29.04 (9.7)
ACRC500/ACRP500 44.3 (151000) 40.7 (139000) 0.92 1.6 (25.9) 66 (21.95)
7.7°C (14°F)
ACRC100 14.9 (51000) 14.9 (51000) 1.00 0.5 (7.8) 19.54 (6.5)
ACRC500/ACRP500 40.8 (139000) 37.9 (129000) 0.93 1.3 (20.6) 42 (14.1)
8.8°C (16°F)
ACRC100 13.8 (47000) 13.8 (47000) 1.00 0.4 (6.4) 13.52 (4.53)
ACRC500/ACRP500 37.8 (129000) 35.2 (120000) 0.93 1.1 (16.8) 29 (9.5)
10°C (18°F)
ACRC100 12.6 (43000) 12.6 (43000) 1.00 0.33 (5.2) 9.63 (3.2)
ACRC500/ACRP500 34.6 (118000) 32.5 (111000) 0.94 0.9 (13.8) 19 (6.5)
11.1°C (20°F)
ACRC100 11.4 (39000) 11.4 (39000) 1.00 0.27 (4.3) 6.93 (2.3)
ACRC500/ACRP500 31.8 (109000) 29.9 (102000) 0.94 0.7 (11.5) 14 (4.6)
29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)
5.5°C (10°F) ACRC100 21.1 (72000) 21.1 (71000) 0.99 0.96 (15.2) 66.05 (22.14)
6.6°C (12°F)
ACRC100 19.6 (67000) 19.6 (67000) 1.00 0.75 (11.8) 41.47 (13.9)
ACRC500/ACRP500 50.8 (174000) 47.8 (163000) 0.94 1.9 (29.5) 84 (28.4)
7.7°C (14°F)
ACRC100 18.7 (64000) 18.7 (64000) 1.00 0.61 (9.7) 28.85 (9.7)
ACRC500/ACRP500 47.7 (163000) 44.8 (153000) 0.94 1.5 (23.9) 56 (18.7)
8.8°C (16°F)
ACRC100 17.9 (61000) 17.9 (61000) 1.00 0.51 (8.1) 20.71 (6.9)
ACRC500/ACRP500 44.1 (151000) 41.9 (143000) 0.95 1.2 (19.4) 38 (12.5)
10°C (18°F)
ACRC100 17.0 (58000) 17.0 (58000) 1.00 0.44 (6.9) 15.54 (5.3)
ACRC500/ACRP500 41.2 (141000) 39.1 (134000) 0.95 1.0 (16.2) 26 (8.8)
11.1°C (20°F)
ACRC100 16.4 (56000) 16.4 (56000) 1.00 0.38 (5.9) 11.96 (3.9)
ACRC500/ACRP500 37.8 (129000) 36.3 (124000) 0.96 0.8 (13.5) 19 (6.2)
32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)
5.5°C (10°F) ACRC100 24.9 (85000) 24.9 (85000) 1.00 1.12 (17.7) 87.77 (29.3)
6.6°C (12°F) ACRC100 23.4 (80000) 23.4 (80000) 1.00 0.88 (13.9) 56.08 (18.7)
7.7°C (14°F)
ACRC100 22.8 (78000) 22.8 (78000) 1.00 0.73 (11.6) 39.84 (13.4)
ACRC500/ACRP500 54.5 (186000) 52.3 (179000) 0.96 1.7 (27.1) 71 (23.8)
8.8°C (16°F)
ACRC100 22.0 (75000) 22.0 (75000) 1.00 0.62 (9.8) 29.34 (9.9)
ACRC500/ACRP500 51.4 (175000) 49.3 (168000) 0.96 1.4 (22.4) 49 (16.6)
10°C (18°F)
ACRC100 21.4 (73000) 21.4 (73000) 1.00 0.54 (8.5) 22.73 (7.6)
ACRC500/ACRP500 47.8 (163000) 46.3 (158000) 0.97 1.2 (18.6) 35 (11.6)
11.1°C (20°F)
ACRC100 21.1 (72000) 21.1 (72000) 1.00 0.48 (7.5) 18.17 (6.01)
ACRC500/ACRP500 44.8 (153000) 43.4 (148000) 0.97 1.0 (15.7) 25 (8.32)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC InRow and is the answer not in the manual?

APC InRow Specifications

General IconGeneral
RefrigerantR410A
MountingIn-row
Humidity Range20% to 80% RH
AirflowVaries by model (e.g., 1, 500 to 6, 000 CFM)
Power Supply208/230V or 400/480V, 3-phase
Operating Temperature Range65°F to 95°F (18°C to 35°C)