990-4618A-001 InRow™ Chilled Water Air Conditioners Technical Specifications 33
Note: All values are accurate to ± 0.73 kW (2500 BTU/hr) and based on full speed with standard filters.
Note: Any CW flow rate of 3.9 GPM-5.0 GPM may have increased error in Flow Rate and Power Calculation. A Fluid Flow
Fault may result. Any flow rate under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
Note: For ACRC500/ACRP500 series, reduce airflow and cooling capacity specifications by 7% for cooling units run
at low input voltage (380V).
35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)
5.5°C (10°F) ACRC100 18.7 (64000) 18.7 (64000) 1.00 0.86 (13.6) 53.44 (17.9)
6.6°C (12°F)
ACRC100 17.0 (58000) 17.0 (58000) 1.00 0.65 (10.3) 32.16 (10.8)
ACRC500/ACRP500 44.2 (151000) 44.2 (151000) 1.00 1.6 (25.9) 66 (21.9)
7.7°C (14°F) ACRC500/ACRP500 40.8 (139000) 40.8 (139000) 1.00 1.3 (20.6) 42 (14.1)
8.8°C (16°F) ACRC500/ACRP500 37.5 (128000) 37.5 (128000) 1.00 1.1 (16.7) 28 (9.5)
37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)
5.5°C (10°F) ACRC100 22.8 (78000) 22.8 (78000) 1.00 1.03 (16.2) 74.93 (25.1)
6.6°C (12°F) ACRC100 21.4 (73000) 21.4 (73000) 1.00 0.8 (12.7) 47.23 (15.9)
7.7°C (14°F) ACRC500/ACRP500 49.8 (170000) 49.8 (170000) 1.00 1.6 (24.8) 60 (20.1)
40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)
5.5°C (10°F) ACRC100 26.1 (89000) 26.1 (89000) 1.00 1.17 (18.5) 96.31 (32.3)
7.7°C (14°F) ACRC500/ACRP500 59.7 (204000) 59.7 (204000) 1.00 1.9 (29.5) 84 (28.2)
Temperature
DB, WB
°C (°F)
CW
Delta T
°C (°F)
Model Series
Total Net Capacity
Sensible Net
Capacity
Sensible
Heat Ratio
CW Flow
Rate
Total CW
Pressure Drop
kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O)