34 InRow™ Chilled Water Air Conditioners Technical Specifications 990-4618A-001
Performance Specifications 15.5°C (60°F) EWT
Note: All values are accurate to ± 0.73 kW (2500 BTU/hr) and based on full speed with standard filters.
Note: Any CW flow rate of 3.9 GPM-5.0 GPM may have increased error in Flow Rate and Power Calculation. A Fluid Flow
Fault may result. Any flow rate under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
Note: For ACRC500/ACRP500 series, reduce airflow and cooling capacity specifications by 7% for cooling units run
at low input voltage (380V).
Temperature
DB, WB
°C (°F)
CW Delta T
°C (°F)
Model Series
Total Net Capacity
Sensible Net
Capacity
Sensible
Heat Ratio
CW Flow
Rate
Total CW
Pressure Drop
kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O)
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
5.5°C (10°F)
ACRC100 5.6 (19000) 5.6 (19000) 1.00 0.28 (4.4) 7.28 (2.5)
ACRC500/ACRP500 17.5 (60000) 17.5 (60000) 1.00 0.9 (13.5) 19 (6.2)
6.6°C (12°F)
ACRC100 3.5 (12000) 3.5 (12000) 1.00 0.17 (2.7) 3.16 (1.2)
ACRC500/ACRP500 15.2 (52000) 15.2 (52000) 1.00 0.6 (10.0) 11 (3.7)
7.7°C (14°F)
ACRC100 3.5 (12000) 3.5 (12000) 1.00 0.15 (2.3) 2.55 (0.9)
ACRC500/ACRP500 13.1 (45000) 13.1 (45000) 1.00 0.5 (7.6) 6 (2.1)
8.8°C (16°F) ACRC500/ACRP500 11.1 (38000) 11.1 (38000) 1.00 0.4 (5.8) 4 (1.4)
10°C (18°F) ACRC500/ACRP500 9.3 (32000) 9.3 (32000) 1.00 0.3 (4.5) 3 (0.9)
11.1°C (20°F) ACRC500/ACRP500 7.7 (26000) 7.7 (26000) 1.00 0.2 (3.5) 2 (0.5)
29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)
5.5°C (10°F)
ACRC100 9.7 (33000) 9.7 (33000) 1.00 0.46 (7.3) 17.33 (5.8)
ACRC500/ACRP500 23.8 (81000) 23.8 (81000) 1.00 1.1 (17.7) 31 (10.4)
6.6°C (12°F)
ACRC100 8.2 (28000) 8.2 (28000) 1.00 0.33 (5.2) 9.63 (3.2)
ACRC500/ACRP500 21.1 (72000) 21.1 (72000) 1.00 0.8 (13.2) 18 (6.01)
7.7°C (14°F)
ACRC100 6.4 (22000) 6.4 (22000) 1.00 0.23 (3.7) 5.3 (1.8)
ACRC500/ACRP500 18.5 (63000) 18.5 (63000) 1.00 0.6 (10.1) 11 (3.7)
8.8°C (16°F) ACRC500/ACRP500 16.1 (55000) 16.1 (55000) 1.00 0.5 (7.9) 7 (2.3)
32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)
5.5°C (10°F)
ACRC100 13.8 (47000) 13.8 (47000) 1.00 0.64 (10.1) 31.09 (10.4)
ACRC500/ACRP500 31.5 (108000) 31.5 (108000) 1.00 1.4 (22.8) 51 (17.1)
6.6°C (12°F)
ACRC100 12.6 (43000) 12.6 (43000) 1.00 0.49 (7.7) 18.94 (6.2)
ACRC500/ACRP500 28.3 (97000) 28.3 (97000) 1.00 1.1 (17.2) 30 (9.9)
7.7°C (14°F) ACRC100 11.1 (38000) 11.1 (38000) 1.00 0.37 (5.9) 11.94 (3.9)
35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)
5.5°C (10°F)
ACRC100 17.3 (59000) 17.3 (59000) 1.00 0.79 (12.5) 46.17 (15.5)
ACRC500/ACRP500 40.6 (139000) 40.6 (139000) 1.00 1.8 (28.7) 80 (26.8)