990-4618A-001 InRow™ Chilled Water Air Conditioners Technical Specifications 35
Performance Data—General
ACRC100 series
Maximum flow rate is 1.53 l/s (20.5 GPM) for continuous operation. May be exceeded by 25% for peak loads.
Maximum working pressure for the unit is 2068.4 kPa (300 psig).
†Maximum distance includes the maximum lift.
*Example: Performance at 29.4°C DB, 18.1°C WB (85° DB, 64.5°F WB) with a 7.2°C (45°F) EWT, and a 5.5°C (10°F) CW
delta T is 18.2 kW (62000 BTU/hr) with the standard filter. Using a 50-mm (2-in) pleated filter with single fan failure, the
performance of the unit would be 18.2 X 0.91 = 16.56 kW (62000 x.91 = 56420 BTU/hr).
MODULATING VALVES
Size 3 Way Ball Valve – NPT mm (in) (Cv)
19.05 (3/4) (27)
AIR SYSTEM
200-mm (7.9-in)
MIXED FLOW DIRECT DRIVE DC
TUBEAXIAL FANS
Standard
Filter
50-mm (2-in)
Pleated Filter
Standard Filter
with Single
Fan Stopped
50-mm (2-in)
Pleated Filter with
Single Fan Stopped
Air Volume - l/s (SCFM) 1380 (2900) 1265 (2680) 1218 (2580) 1114 (2360)
Fan Motor - Watts (each) 115 115 115 115
Number of Fans 8 8 7 7
Performance Specifications Table
Multiplier*
1.0 .96 .94 .91
COOLING COIL - COPPER TUBE/ALUMINUM FIN
Face Area - m
2
(ft
2
) 0.510 (5.5)
Rows Deep 3
Face Velocity - m/s (FPM) 2.67 (527)
FILTERS - WASHABLE (STANDARD)
Quantity 2
Size - mm (in) 238 x 933 (9.375 x 36.75)
Depth - mm (in) 13 (1/2)
Efficiency (%) <20% MERV 1
FILTERS - PLEATED (OPTIONAL)
Size - mm (in) 238 x 933 (9.375 x 36.75)
Depth - mm (in) 51 (2)
Efficiency (%) 30% MERV 8
PHYSICAL DATA
Net Weight - kg (lbs) 162.73 (358)
Operating Weight – kg (lbs) 170 (376)
Height - mm (in) 1991.00 (78.39)
Width - mm (in) 300.00 (11.81)
Depth - mm (in) 1070 (42.13)
CONNECTION SIZES
Chilled Water
Supply Line - mm (in) 25.4 (1) NPT Connection
Return Line - mm (in) 25.4 (1) NPT Connection
Condensate Drain Drain Line -mm (in) 4.77 (3/16) ID, 6.35 (1/4) OD
DUAL FLOAT CONDENSATE MANAGEMENT
Flow Rate- L/hr (GPH) 5 (1.3)
Maximum Distance - m (ft)
†
15.2 (50)
Maximum Lift - m (ft) 4.9 (16)