38 InRow™ Chilled Water Air Conditioners Technical Specifications 990-4618A-001
Sound Performance Data
*Weighted Sound Pressure dBA in a 232.2 m
3
(8,200 ft
3
) room at 1.8 m (6 ft) distance.
*Weighted Sound Pressure dBA in a 232.2 m
3
(8,200 ft
3
) room at 1.8 m (6 ft) distance.
ACRC100 Series Tested Sound Data
Fan
Speed%
Airflow l/s
(SCFM)
Sound Power dB at Frequency Hz – 10
-12
W
Lp Sound
Pressure dB
20 μPa*
125 250 500 1000 2000 4000 8000 dBA dBA
45 849 (1800) 63.5 69.5 71.0 76.0 69.0 60.5 54.5 78.0 66.3
55 1014 (2150) 66.5 77.5 76.0 79.0 75.0 69.0 62.5 82.2 70.6
70 1109 (2350) 68.5 81.5 78.5 79.5 77.5 73.0 67.5 84.2 72.4
85 1274 (2700) 69.5 83.0 80.0 82.0 78.5 75.5 69.5 86.0 74.3
100 1368 (2900) 71.5 82.0 84.5 86.5 81.5 79.0 73.5 89.5 78.1
ACRC500 Series Tested Sound Data
Fan
Speed%
Airflow l/s
(SCFM)
Sound Power dB at Frequency Hz re: 10
-12
W
Lp Sound
Pressure dB
20 μPa*
125 250 500 1000 2000 4000 8000 dBA dBA
35 1130 (2500) 69.5 37.5 63.5 60.0 54.0 47.5 40.0 65.4 54.9
50 1790 (3800) 84.0 79.0 75.5 69.5 67.5 58.5 53.5 76.9 66.8
70 2550 (5400) 92.0 87.0 83.5 79.0 74.5 69.5 63.5 85.9 75.0
85 3040 (6450) 92.0 95.0 89.0 84.5 79.0 74.5 69.0 90.6 80.7
100 3260 (6900) 90.0 96.5 90.5 85.0 80.5 76.0 70.5 91.7 81.9