990-4618A-001 InRow™ Chilled Water Air Conditioners Technical Specifications 39
Electrical Data
*ACRC500 and ACRC502 have the option of being hardwired.
Note: Above data is based on maximum operating condition.
Note: Installation must comply with local and/or national electrical codes.
MCA—Minimum Circuit Ampacity
MOP—Maximum Overcurrent Protection
FLA—Full Load Amps
Model Power MCA MOP FLA Power
kw
Power Connection
Voltage Phase Frequency
ACRC100 100–120 1 50/60 N/A N/A N/A 1.1
NEMA L5-20P
ACRC103 200–240 1 50/60 N/A N/A N/A 1
IEC-309 16 A
ACRC500* 200–240 3 50/60 11 15 N/A 3.2
NEMA L21-20P
(Top-Wired Only)
ACRC501 460–480 3 50/60 7 15 N/A 3.3 Hard-wired
ACRC502* 380–415 3 50/60 7 15 6 3
IEC-309 16 A
(Top-wired Only)
ACRP500 200–240 3 50/60 46.8 50 N/A 14 Hard-wired
ACRP501 460–480 3 50/60 24.8 30 N/A 14 Hard-wired
ACRP502 380–415 3 50/60 N/A N/A 24** 15 Hard-wired