37Metered Rack PDU User’s Guide
humMin
Access: Administrator, Device User
Description: Set or view the minimum humidity threshold as a percent of the relative humidity.
Example 1: To view the minimum humidity threshold, type:
apc> humMin
E000: Success
6 %RH
Example 2: To set the minimum humidity threshold, type:
apc> humMin 8
E000: Success
humReading
Access: Administrator, Device User
Description: View the humidity value from the sensor.
Example: To view the humidity value, type:
apc> humReading
E000: Success
25 %RH
phLowLoad
Access: Administrator, Device User
Description: Set or view the phase low-load threshold in kilowatts. To specify phases, choose from the
following options. Type: all, a single phase, a range, or a comma separated list of phases.
Example 1: To set the phase low-load threshold for all phases to 1 kW, type:
apc> phLowLoad all 1
E000: Success
Example 2: To view the phase low-load threshold for phases 1 through 3, type:
apc> phLowLoad 1-3
E000: Success
1: 1 A
2: 1 A
3: 1 A