Metered Rack PDU User’s Guide38
phNearOver
Access: Administrator, Device User
Description: Set or view the phase near-overload threshold in kilowatts. To specify phases, choose
from the following options. Type:
all, a single phase, a range, or a comma separated list of phases.
Example 1: To set the near-overload threshold for all phases to 10 kW, type:
apc> phNearOver all 10
E000: Success
Example 2: To view the near-overload threshold for phases 1 through 3, type:
apc> phNearOver 1-3
E000: Success
1: 10 A
2: 10 A
3: 10 A
phOverLoad
Access: Administrator, Device User
Description: Set or view the phase overload threshold in kilowatts. To specify phases, choose from the
following options. Type: all, a single phase, a range, or a comma separated list of phases.
Example 1: To set the overload threshold for all phases to 13 kW, type:
apc> phOverLoad all 13
E000: Success
Example 2: To view the overload threshold for phases 1 through 3, type:
apc> phOverLoad 1-3
E000: Success
1: 13 A
2: 13 A
3: 13 A