Expansion/Triple Chassis Installation
continued
Step 3: Install
the Network
Management
Card
Caution: If the UPS uses more than one APC management
peripheral, see the supplied Installation of Multiple
Management Cards sheet. You must install the APC
peripherals in the correct order, otherwise the
peripherals may fail to operate properly.
1. If PowerChute plus is installed, stop the PowerChute plus
service and disconnect its cable from the UPS serial port.
2. Use the screws that hold the expansion slot cover in place
to secure the Management Card in the chassis slot.
3. Connect a network interface cable to the Management
Card’s 10/100Base-T network connector.
4. If you are using the optional AC Adapter (AP9505), do
the following:
a. Connect the adapter to the chassis.
b.Connect the adapter to an independent AC input so that
the Management Card can continue to operate if the
UPS is turned off or fails.
5. If neccessary, reconnect the PowerChute plus cable.
6. If neccessary, restart the PowerChute plus service.
7. See “Quick Configuration” on page 9.
Figure 2: Installing a Management Card in a SmartSlot Expansion
Chassis (AP9600)