5.2.6 Converter mode
In converter mode, the UPS would free run with fixed output frequency(50Hz or 60Hz). Once
the mainspoweris loss or abnormal, the UPS would transfer to battery mode and the load is
supplied continuously.
1) The function could be enabled through the LCD setting or the software (Winpower, etc.).
2) The load should be derated to 60% in converter mode.
5.2.7 Warning
When the warning occurs, it illustrates that there are some abnormal problems during the
operation of UPS. Normally the problems are not fataland the UPS continues working, but they
should be paid attention to, or the UPS may fail.
The detailed warning table isshown in chapter of 7.