5.4.5 The control menu
By pressing on the menu of “Control”, the display would enter the next control menu tree.
1) Single UPS turn off: is one command to turn off one UPS which is operated currently
in a parallel system, and other UPSs continue working to supply the load in the parallel
system.
2) Single UPS battery test: is one command to control one UPS which is operated
currently in a parallel system to do the battery test singly, and other UPSs do not do
the battery test.
3) Parallel UPS battery test: is one command to control all UPS in a parallel system to do
the battery test at the same time.
4) Clear EPO status: once EPO status is enabled, the UPS output would be cut off. To
recover to normal status, first EPO connector should be closed, and enter this menu to
clear EPO status, then UPS would stop alarm and recover to Bypass model.And UPS
needs be turned on by manual operation.
5) Reset fault status: when fault occurs, UPS would keep in Fault mode and alarm. To
recover to normal status, enter this menu to reset error status, then UPS would stop
alarm and recover to Bypass mode.And the reason of fault should be checked and
deleted before UPS is turned on again by manual operation.
6) Restore factory settings: all the settings would be recover to default factory settings. It
could only be done in Bypass mode