adjusted to 208VAC.
*The overload capacity would be derated automatically in Line mode while the
circumstance temperature is larger than 35 degree.
2)
Operating Environment
Operating
Temperature
0
o
C to 45
o
C
Operating humidity
< 95%
Altitude
< 1000m*
Storage
temperature
-15
o
C to 50
o
C
*The load capacity should be derated 1% every 100m heightened on the basis of 1000m.
3.2
Typical Backup Time (Typical values at 25°C in minutes)
Model No.
100 % Load
Plus III-6KLRB
5
PlusIII-10KLRB
4
3.3
Unpacking and Inspection
1)
Unpack the packaging and check the package contents. The shipping package
contains:
A UPS
A user manual
A communication cable
A battery cable (for Plus III-6KLRB/PlusIII-10KLRB only)
2)
Inspect the appearance of the UPS to see if there is any damage during
transportation. Do not turn on the unit and notify the carrier and dealer
immediately if there is any damage or lacking of some parts.