APD0602 A140513 Wireless CO Install
CAUTION
It should be noted the installation, operation, testing and maintenance of
the Wireless Carbon Monoxide Alarm is different than smoke detectors. Per
NFPA 720 section 5.3.7.2 the detector shall not be connected to a zone that
signals a re condition (i.e. smoke detectors zones). Therefore, the Wireless
Carbon Monoxide Alarm must be programmed as a non-re zone. See the
control’s Installation Instructions for the appropriate carbon monoxide
zone type to be programmed.
SPECIFICATIONS
Power Source: One 3-volt CR123A Panasonic Lithium Battery (included)
Audible Signal (temp 4 tone): 85 dBA min. in alarm (at 10ft (3m))
Operating Current: 10 µA
Temperature Range: 40°F (4.4°C) to 100°F (37.8°C)
Operating Humidity Range: 15% to 95% Relative Humidity, non-condensing
Pending Agency Listings: UL standard 2075, UL 2034 and CSA 6.19-01