2
INST APD0601 A140513 Wireless Smoke Heat Alarm Install Guide
Status LEDs
Sounder
(do not pulse the sounder
and LED concurrently)
Normal Green ash every 12 seconds Off
Heat Alarm Red ash every 1 second ANSI S3.41 temporal 3
Heat Test Red ash every 1 second ANSI S3.41 temporal 3
Smoke Alarm Red ash every 1 second ANSI S3.41 temporal 3
(press button to hush
for 5-10 minutes)
Smoke Test Red ash every 1 second ANSI S3.41 temporal 3
(press button to hush
for 5-10 minutes)
Test Alarm Red ash every 1 second ANSI S3.41 temporal 3
Freeze Warning 3 yellow ashes
every 4 seconds
Off
Detector Trouble Yellow ash every 4 seconds One chirp every 48 seconds
Low Battery Yellow ash every 12 seconds One chirp every 48
seconds (press button
to hush for 12 hours)
Detector Dirty Yellow ash every 8 seconds One chirp every 48 seconds
Power-up Red, yellow, green
ash sequence
One chirp at the end
of power-up sequence
Tamper Red, yellow, green ash
sequence every 12 seconds
Off
The Wireless Smoke Heat Alarm contains a sounder which generates the
ANSI S3.41 temporal 3 pattern in an alarm condition. In alarm, a message
is also sent to the control panel and the detector’s ID is displayed at
the console. During an alarm condition, pressing the detector’s hush
button will silence the sounder (see table below). The mounting base
installation is simpli ed by the incorporation of features compatible
for both drywall fasteners (not supplied) and other methods.
Tricolored LED (red, yellow, green) and a sounder on the detector
provide local visual and audible indication of the detector’s status as
listed in Table 1.
During initial power-up the LED blinks alternately red, yellow then
green. It takes about 8 seconds for the detector to stabilize.
After power-up has completed and the detector is functioning normally,
the green LED blinks once every 12 seconds.
Detector Trouble: When the detector has a general fault, the yellow LED
blinks once every four seconds and there is a chirp every 48 seconds.
After 12 hours the panel will display a loss of supervision message.
Table 1. Detector status and indication