EasyManuals Logo

Apollo 65 Series User Manual

Apollo 65 Series
4 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #2 background imageLoading...
Page #2 background image
Sensor window contamination
It is important to keep the sensor window clean and checks should be carried out at
regular intervalsdetermined locally according to the type and degree of contamination
encountered– to ensure optimal performance of the ame detector.
It is recommended that the ame detector be disabled when the window is being
cleaned.
Applications for Marine UV Flame Detectors
Flame detectors are used when detection is required to be unaffected by convection cur-
rents, draughts or wind; tolerant of fumes, vapours, responsive to a ame up to 25m away
and fast reacting.
Typical applications examples are:
• engine room
factory
garage
hospital
printing
warehouse
Applications and locations to avoid:
outdoors
• open windows and doorways
• electric sparks, arcs and welding
• UV lamps
• radiation sources
• prolonged ambient temperatures above 60°C
• exposure to water and ice
• gathering of dust or oil lms on sensor window
ood or spot lighting falling directly on UV optics
• obstructions to eld of view
10. Inform all appropriate personnel on completion of the maintenance work and if
necessary record this work.
Technical Data
Supply voltage 1233V DC (polarity insensitive)
Quiescent current 550μA
Alarm voltage 6 to 33V
Normal alarm current 61mA at 28V
54mA at 24V
20mA at 10V
Remote output characteristics Remote is a current sink to the negative
line limited to 17mA
Alarm indicator Red, Light Emitting Diode (LED)
Design alarm load 420Ω in series with a 2V drop
Hold voltage 6V (min)
Holding current 10mA (min)
Minimum voltage required 12V
to illuminate indicators
Alarm reset voltage <1V
Alarm reset time 1 second
Operating Range 25m for 0.1m² n-heptane re, EN54-10, class 1
2m for 0.1m² n-heptane re, EN54-10, class 3
Sensitivity Switch Options class 1 (default) and class 3, as in EN54-10,
clause 5.5
Field of view 90° cone
Spectral response UV 185 to 260nm
Operating temperature 40°C to +70°C (no condensation or icing)
Storage temperature 40°C to +85°C
Relative humidity 0-95% (no condensation)
IP rating 66
Housing material White polycarbonate V-0 rated to UL94
Dimensions 100mm diameter
40mm height, 48mm in base
Weight 150g detector, 210g in base
Additional Equipment
Stainless steel adjustable mount Part no. 29600-458
with deck head box
Portable ame detector test unit Part no. 29600-226
Deckhead Mounting Box Part no. 45681-217
2 7
www.acornfiresecurity.com
www.acornfiresecurity.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Apollo 65 Series and is the answer not in the manual?

Apollo 65 Series Specifications

General IconGeneral
Mechanical Life10, 000, 000 operations
Ambient Temperature-40°C to +85°C
Contact Voltage Rating DC30V
Coil Voltage5V, 12V, 24V DC
Electrical Life100, 000 operations
Insulation Resistance1000MΩ min
Vibration Resistance10 to 55 Hz, 1.5mm