CLEAVER-BROOKS
MODEL CB, CB-LE
PACKAGED BOILER
125 through 200 HP
Fuel: Light Oil, Heavy Oil, Gas or Combination
Operation, Service, and Parts Manual
Compliments of Power Mechanical, Inc.
Used Boilers
Rental Boilers

Table of Contents

Questions and Answers

  • A
    Adrian YorkAug 22, 2025
    Why Aqua-Chem Cleaver-Brooks CB Boiler burner stays in low fire?
    • W
      Warren ChoiAug 22, 2025
      If the burner in your Aqua-Chem Boiler stays in low fire, it could be due to: * Pressure or temperature above modulating control setting. * Manual-automatic switch in wrong position. * Inoperative modulating motor. * Defective modulating control. * Binding or loose linkage, cams, setscrews, etc.
  • P
    Paula HarmonAug 31, 2025
    How to troubleshoot modulating motor that does not operate in Aqua-Chem Cleaver-Brooks CB Boiler?
    • C
      Catherine NavarroAug 31, 2025
      If the modulating motor in your Aqua-Chem Boiler isn't working, consider these possibilities: * Manual-automatic switch in wrong position. * Linkage loose or jammed. * If the motor doesn't drive to open or close during pre-purge or close on burner shutdown: the motor could be defective, there might be a loose electrical connection, or the damper motor transformer could be defective. * If the motor doesn't operate on demand: the manual/automatic switch could be in the wrong position, the modulating control might be improperly set or inoperative, the motor could be defective, there might be a loose electrical connection, or the damper motor transformer could be defective.
  • J
    Jeffrey Anderson Jr.Nov 10, 2025
    Why Aqua-Chem Cleaver-Brooks CB has no ignition?
    • C
      Cynthia HickmanNov 10, 2025
      If your Aqua-Chem Boiler has no ignition, possible causes include: * **Lack of spark:** This may be due to a grounded electrode, cracked porcelain, improper electrode setting, loose terminal on the ignition cable, a shorted cable, an inoperative ignition transformer, or insufficient voltage at the pilot ignition circuit terminal. * **Spark but no flame:** This could be due to a lack of fuel, an inoperative pilot solenoid, insufficient voltage at the pilot ignition circuit terminal, or too much air. * **Low fire switch open:** The damper motor may not be closed, the cam might have slipped, or the switch could be defective. The damper could also be jammed, or the linkage binding. * **Running interlock circuit not completed:** Combustion or atomizing air proving switches could be def...

Aqua-Chem Cleaver-Brooks CB Series Specifications

General IconGeneral
PressureUp to 300 psi
TypeFiretube
ApplicationIndustrial, Commercial
Fuel TypeNatural Gas
Capacity150 - 800 hp
Steam OutputUp to 28, 000 lbs/hr
Heat Exchanger MaterialCarbon Steel