TankmaticSmartRelay
Aquatech‐PressmainInstructionmanual\TankmaticsmartrelayMG‐LT
3
0.GENERALSAFETYINFORMATION
Theseinstructionsareintendedfortheinstaller/operator/user/maintenanceofthisequipment
andmustbekeptwiththeequipment,forthelifeoftheequipmentandmadeavailabletoall
persons.PleasereadGENERALSAFETYINFORMATION0.0,WARNINGS0.1andCAUTIONS0.2,0.3&
0.4beforedoinganythingelse,andthenfollowthemcarefully.
Theunitmustonlybeinstalled/operated/used/maintainedbyacompetentperson;Acompetent
personissomeonewhoistechnicallycompetentandfamiliarwithsafetypracticesandthehazards
involved.
HydraulicAccumulators/ExpansionVesselsinstalledaspartof/inconjunctionwiththisequipment,
withPressurexVolumeabove250Bar‐litres,requireregularformalinspectionbyacompetent
person.ThisisaLegalRequirementunderthe“PressureSystemsSafetyRegulations”(PSSR)and
theOwner/Usershouldbemadeawareoftheirresponsibilityforthis.(seesection3.Servicing).
Failuretoinstall/operate/use/maintaintheequipmentasrecommendedbelowcouldcause
damagetotheequipmentanyanythingsubsequentlyconnectedtoit,andinvalidatethewarranty
providedbyAquaTech‐Pressmaintothebuyer.
Anydamagecausedtotheequipmentbymisapplication,mishandlingormisusecouldleadtorisk
ofElectrocution,Burns,Fire,Floodingorinjurytopeopleorpropertydependentuponthe
circumstancesinvolved.
ThisequipmentMAYcontainmoving/rotatingpartsthatmustremainguarded.Removalofor
missingguardscouldleadtoseriouspersonalinjury.
Thisequipmentautomaticallyrestartsafterapowerinterruption.
Weacceptnoresponsibilityorliabilityforanyconsequencesordamage/lossesdueto
misapplication,mishandlingormisuseoftheequipment.
Itshouldbenotedthattheassemblyofpressureequipmentonsiteundertheresponsibilityofthe
user(orhisrepresentative)isnotsubjecttothePressureEquipmentDirective97/23/EC.(National
legislationcoveringassemblyonsitewillapply)
Thelatestversionofthisinstructionmanualwithuptodatesafetyinformationcanbedownloaded
fromourwebsiteatwww.aquatechpressmain.co.uk
0.1 WARNINGS
0.1.1 Donottouchanylivepartsforatleast5minutesafterswitchingofftheelectricitysupply.Failureto
observethiswillconstituteasevereElectricshockand/orBurnshazardandmaybelethal.
0.1.2 Theequipmentisonlysuitableforearthreferencedsuppliesandmustbepermanentlyearthedto
avoidElectricshockhazard.
0.1.3 WithequipmentisolatorOFF,mainsvoltagemaystillbepresentfromBMSsystem.Thisconstitutes
anElectricshockhazard.
0.1.4 Emergencystopbuttondoesnotremovedangerousvoltagesfromcontrolpanel/pumpmotor
assemblies.ThisconstitutesanElectricshockhazard.
0.1.5 Metalparts(e.g.heatsinks)mayreachtemperaturesof90degreescentigradeandwillconstitutea
Burnshazard.
0.1.6 Someequipmentisdesignedtooperatewithliquidtemperaturesupto150degreescentigradeand
willconstituteaBurns/scaldinghazard.