17) Symptom: LCD on the remote controller displays “CHECK H01, H02, H03”. (PC compressor
current detection)
* Please check the related part described in the following chart after confirming the code setting
(S4) of the outdoor unit’s capacity on the PCB in the outdoor unit.
18) Check the indoor unit (When the alarm of communication failure is not activated)
If the electronic control valve failure occurred in Flexible Combination system (simultaneous operation system),
one indoor unit would not be operated normally, then the other units won’t be operated either. Due to this, try
to detect the troubled unit and correct it.
0346_M_I
CHECK H02”
DISPLAY
Compressor lock detection
¥ Insufficient voltage
¥
Comp. motor magnetic contactor
defect
¥ Refrigerant over-charged
Start
Compressor lock
“CHECK H01” display
Compressor overload
detection
¥ L3 phase wire disconnected
¥
Comp. motor magnetic contactor
defect
¥ Outdoor unit PCB defect
CHECK H03” display
Compressor current detection
circuit defect
Normal
No
Failure in the electronic
control valve activation.
No
Replace the sensor.
Operate the unit in
cooling mode.
(30 minutes after its operation)
¥ Cooled air comes out.
¥ Is the temperature of each indoor coil sensor almost
the same? (Refer to the sensor temperature
display function of the remote controller.)
¥ Does each indoor coil sensor detect the temperature
correctly? (Is there any leakage from the pipe of the
temperature detection section?)
Yes
Yes