Fan Coil Unit Wall Mounted Type
Phenomenon Troubleshooting
Cracking noise:
This is the sound of friction caused by expansion and/
or contraction of panel or other parts due to the change
of temperature.
The unit can not be started up:
Breaking off
Is the power cut off?
Is the power plug loose? (If applicable )
Is the circuit protection device tripped off?
Is voltage higher or lower?(Tested by professionals)
Is the TIMER correctly used?
Cooling/Heating effect is poor:
Is temperature setting appropriate?
Is the inlet or outlet blocked?
Is the lter dirty?
Is the window or the door open?
Is low fan speed set?
Are there heat sources in the room?
Remote controller is not available:
Check if there is magnetic or electrical interference
near the unit that may affecting operation of the
controller. In this case, pull the plug out and reinsert it.
Is the remote controller within its operating range or
obstructed? Check the condition of the batteries and
replace them if necessary.
Check if the remote controller is damaged.
Water leakage of FCU.
The humidity is high.
Condensate overows.
Drain hose is loose.
Noise from FCU. The noise emitted when the fan is switching on or off.
FCU can not blow air:
In HEAT mode, when the temperature of FCU heat
exchanger is very low, air flow is stopped in order to
prevent cold air.
In COOL mode, when the temperature of FCU heat
exchanger is very high, air flow is stopped in order to
prevent hot air.
Moisture on air outlet :
If the unit operates at high humidity for a long time,
moisture will be generated onthe air outlet grill and then
drip off.
C5:Malfunction of connector jumper:
Check if the connector jumper contacts properly. If the
PCB is to be replaced, please take off the old for the
new PCB.